List of parameters
Parameters
1-453
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Enters the dynamic torque setpoint for the low-speed range for sensorless vector control (SLVC). This parameter is
entered as a percentage referred to the rated motor torque (r0333).
Note:
When accelerating and braking p1611 is added to p1610 and the resulting total torque is converted into an appro-
priate current setpoint and controlled.
For pure accelerating torques, it is always favorable to use the torque pre-control of the speed controller (p1496).
Description:
Sets the current setpoint for controlled (open-loop) sensorless operation.
Note:
The value is effective at speeds less than p1755 and represents a reserve for a possibly existing load torque or
torque error in the moment of inertia.
Description:
Sets the smoothing time for the current setpoint.
The current setpoint is generated from p1610 and p1611.
Note:
This parameter is only effective in the range where current is impressed for sensorless vector control.
Description:
Displays the pre-control value of the current model controller. It involves a magnetizing current in the de-direction.
p1611[0...n]
Supplementary accelerating torque (SLVC) / M_suppl_accel
VECTOR (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
6722
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL, FEM
Expert list:
1
Min Max
Factory
setting
0.0 [%]
200.0 [%]
0.0 [%]
p1612[0...n]
Current setpoint, open-loop control, sensorless / I_setCtrSensorless
SERVO
Can be changed:
U, T
Calculated:
CALC_MOD_REG
Access level:
2
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
6_2
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [Arms]
10000.00 [Arms]
0.00 [Arms]
p1616[0...n]
Current setpoint smoothing time / I_set T_smooth
VECTOR (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_REG
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
6722
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL, FEM
Expert list:
1
Min Max
Factory
setting
4 [ms]
10000 [ms]
40 [ms]
r1618
Current model controller, pre-control / I_mod_ctrl prectrl
VECTOR (n/M)
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
6_2
Unit selection:
p0505
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...