List of parameters
Parameters
1-59
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Displays missing enable signals that are preventing the closed-loop drive control from being commissioned.
Dependency:
Refer to: r0002
Note:
The value r0046 = 0 indicates that all enable signals for this drive are present.
Bit 00 = 1 (enable signal missing), if:
- the signal source in p0840 is a 0 signal.
- there is a power-on inhibit.
Bit 01 = 1 (enable signal missing), if:
- the signal source in p0844 or p0845 is a 0 signal.
Bit 02 = 1 (enable signal missing), if:
- the signal source in p0848 or p0849 is a 0 signal.
Bit 03 = 1 (enable signal missing), if:
- the signal source in p0852 is a 0 signal.
Bit 04 =1 (armature short-circuit active), if:
- the signal source in p1230 has a 1 signal
Bit 05, Bit 06: Being prepared
Bit 08 = 1 (enable signal missing), if:
- the pulse enable via terminal EP is missing (booksize: X21, chassis: X41).
Bit 09 = 1 (enable signal missing), if:
- the signal source in p0864 is a 0 signal.
r0046.0...31
CO/BO: Missing enable sig / Missing enable sig
SERVO (Lin)
Can be changed:
-
Calculated:
-
Access level:
1
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
2634
P-Group:
Displays, signals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
OFF1 enable missing
Yes
No
-
01
OFF2 enable missing
Yes
No
-
02
OFF3 enable missing
Yes
No
-
03
Enable operation missing
Yes
No
-
04
Armature short-circuit / DC current brake,
enable missing
Yes
No
7014,
7016
05
STOP2 enable missing
Yes
No
-
06
STOP1 enable missing
Yes
No
-
08
EP terminals enable missing
Yes
No
-
09
Infeed enable missing
Yes
No
-
10
Ramp-function generator enable missing
Yes
No
-
11
Ramp-function generator start missing
Yes
No
-
12
Setpoint enable missing
Yes
No
-
16
OFF1 enable internal missing
Yes
No
-
17
OFF2 enable internal missing
Yes
No
-
18
OFF3 enable internal missing
Yes
No
-
19
Pulse enable internal missing
Yes
No
-
20
Armature short-circuit/DC current brake
internal enable missing
Yes
No
7014,
7016
21
STOP2 enable internal missing
Yes
No
-
22
STOP1 enable internal missing
Yes
No
-
25
Function bypass active
Yes
No
-
26
Drive inactive or not operational
Yes
No
-
27
Demagnetization not completed
Yes
No
-
28
Brake open missing
Yes
No
-
29
Cooling system ready signal missing
Yes
No
-
30
Velocity controller inhibited
Yes
No
-
31
Jog setpoint active
Yes
No
-
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...