Parameters
List of parameters
1-666
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the signal source to define how values are transferred in the operating mode "direct setpoint input/MDI".
BI: p2649 = 1 signal
Values are continually transferred (refer to parameter under dependency).
BI: p2649 = 0 signal
The values are transferred for BI: p2650 = 0/1 signal.
Dependency:
Refer to: p2642, p2643, p2644, p2645, p2648, p2650, p2651, p2652
Caution:
For BI: p2649 = 1 signal, the following applies:
Motion starts without any explicit control signal.
Note:
p2649 can only be changed for p0922 (p2079) = 999.
Description:
Sets the signal source to accept the values for edge-triggered selection (BI: p2649 = 0 signal) in the operating mode
"direct setpoint input/MDI".
BI: p2650 = 0/1 signal and BI: p2649 = 0 signal
Values are accepted, edge-triggered (refer to parameter under dependency).
Dependency:
Refer to: p2640, p2641, p2642, p2643, p2644, p2645, p2648, p2649, p2651, p2652, r2684
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
The status signal r2684.12 = 0/1 signal is used for acknowledgement.
The operating mode "direct setpoint input/MDI" can be influenced via the following signals:
- intermediate stop via BI: p2640.
- reject traversing task via BI: p2641.
Description:
Sets the signal source for the positive direction selection in the operating mode "direct setpoint input/MDI".
Dependency:
Refer to: p2576, p2648, p2649, p2650, p2652, p2653, p2654
Note:
The following applies for "setting-up":
- the traversing direction can be entered using this binector input.
- if both directions (p2651, p2652) are selected, then the axis remains stationary (zero speed).
- if both directions (p2561, p2652) are de-selected, then the axis remains stationary (zero speed).
The following applies for "positioning":
Using binector inputs p2651 and p2652, when the modulo correction (BI: p2576 = 1 signal) is activated and for
absolute positioning (BI: p2648 = 1 signal), the traversing direction is specified as follows:
p2649
BI: EPOS direct setpoint input/MDI transfer type selection / MDI trans_type sel
SERVO (EPOS),
VECTOR (EPOS)
Can be changed:
T
Calculated:
-
Access level:
1
Data type:
Unsigned32 / Binary
Dynamic index:
-
Func. diagram:
3620
P-Group:
Basic positioner
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p2650
BI: EPOS direct setpoint input/MDI setpoint acceptance edge / MDI setp_accept
SERVO (EPOS),
VECTOR (EPOS)
Can be changed:
T
Calculated:
-
Access level:
1
Data type:
Unsigned32 / Binary
Dynamic index:
-
Func. diagram:
3620
P-Group:
Basic positioner
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p2651
BI: EPOS direct setpoint input/MDI direction selection, positive / MDI dir_sel pos
SERVO (EPOS),
VECTOR (EPOS)
Can be changed:
T
Calculated:
-
Access level:
1
Data type:
Unsigned32 / Binary
Dynamic index:
-
Func. diagram:
3620
P-Group:
Basic positioner
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...