![Siemens SINAMICS S Series Скачать руководство пользователя страница 1454](http://html.mh-extra.com/html/siemens/sinamics-s-series/sinamics-s-series_list-manual_12654271454.webp)
Faults and Alarms
List of faults and alarms
3-1454
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Remedy:
Clear alarm:
Set p9496 to 1 or 2
or
de-activate DO
A01319
Inserted component not initialized
Drive object:
A_INF, B_INF, CU_LINK, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41, TM54F_MA,
TM54F_SL, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
The inserted component has still not been initiated, as the pulses are enabled.
Remedy:
Pulse inhibit
A01320
Topology: Drive object number does not exist in configuration
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
A drive object number is missing in p0978
Alarm value (r2124, interpret decimal):
Index of p0101 under which the missing drive object number can be determined.
Remedy:
Set p0009 to 1 and change p0978:
Rules:
- p0978 must include all of the drive object numbers (p0101).
- it is not permissible that a drive object number is repeated.
- by entering a 0, the drive objects with PZD are separated from those without PZD.
- only 2 partial lists are permitted. After the second 0, all values must be 0.
- dummy drive object numbers (255) are only permitted in the first partial list.
A01321
Topology: Drive object number does not exist in configuration
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
p0978 contains a drive object number that does not exist.
Alarm value (r2124, interpret decimal):
Index of p0978 under which the drive object number can be determined.
Remedy:
Set p0009 to 1 and change p0978:
Rules:
- p0978 must include all of the drive object numbers (p0101).
- it is not permissible that a drive object number is repeated.
- by entering a 0, the drive objects with PZD are separated from those without PZD.
- only 2 partial lists are permitted. After the second 0, all values must be 0.
- dummy drive object numbers (255) are only permitted in the first partial list.
A01322
Topology: Drive object number present twice in configuration
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
A drive object number is present more than once in p0978.
Alarm value (r2124, interpret decimal):
Index of p0978 under which the involved drive object number is located.
Remedy:
Set p0009 to 1 and change p0978:
Rules:
- p0978 must include all of the drive object numbers (p0101).
- it is not permissible that a drive object number is repeated.
- by entering a 0, the drive objects with PZD are separated from those without PZD.
- only 2 partial lists are permitted. After the second 0, all values must be 0.
- dummy drive object numbers (255) are only permitted in the first partial list.
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...