Install Telecommunications Cabling
Patch Cord/Jumper Installation and Administration
446
SI Installation and Upgrades
June 2004
Figure 165: Coupled Bonding Conductor
Return to Task List
Figure notes
1
25-Pair Tip & Ring Cables to Cabinets
2
Coupled Bonding Conductor (CBC)
Terminal Block
3
Tie Wraps
4
Cable Shield or Six Spare Pairs
5
Ground on Carbon Block Protector or
Equivalent
6
Trunk Cable to Network Interface
7
10 AWG (#25) (2.5 mm
2
) Wire
8
To Network Cabinets
9
Battery Plant Ground Discharge Bar
for Single-Point Ground
10
Cross-Connect Ground Block
11
Main Distribution Frame (MDF)
12
To Other Cross-Connect Ground
Blocks
13
Approved Ground
14
Coupled Bonding Conductor (CBC)
cbc_gnd_1 PDH 062696
Содержание MCC1
Страница 38: ...Upgrades to Avaya Commnication Manager Made Easy Before you start 38 SI Installation and Upgrades June 2004 ...
Страница 326: ...Installation for MCC1 Multicarrier Cabinets Made Easy 326 SI Installation and Upgrades June 2004 ...
Страница 362: ... Single Carrier Cabinets Made Easy 362 SI Installation and Upgrades June 2004 ...
Страница 498: ...Test the System LED Indicators 498 SI Installation and Upgrades June 2004 ...
Страница 650: ...Add IP Solutions Task list Upgrade a TN802 to a TN802B 650 SI Installation and Upgrades June 2004 ...
Страница 692: ...Install and Administer Trunks Add TN1654 DS1 Converter r only 692 SI Installation and Upgrades June 2004 ...
Страница 770: ...Connecting and Handling Fiber Optic Cables Cleaning Fiber Optic Cables 770 SI Installation and Upgrades June 2004 ...
Страница 784: ...Connector and Cable Diagrams Pinout Charts DS1 Interface Cable H600 307 784 SI Installation and Upgrades June 2004 ...
Страница 792: ...UPS Installation for SCC1 EPN A Carrier Cabinet Task List Install UPS 792 SI Installation and Upgrades June 2004 ...
Страница 874: ...Index Z 874 SI Installation and Upgrades June 2004 ...