Install and Connect MCC1 (Multicarrier) Cabinet
Task List: Connect DC Power and Ground
354
SI Installation and Upgrades
June 2004
Connect External Alarm Cable
Return to Task List
1
Plug the external alarm cable into the connector shown in
Figure 103, External Alarm Cable
Connection,
on page 354.
2
Route the opposite end of the cable to the MDF. The alarm cable is connected to the MDF later.
Figure 103: External Alarm Cable Connection
Check Commercial Power and Connect AC Power
Return to Task List
Before powering up the system, check the AC power using a KS-20599 digital voltmeter (DVM) (or
equivalent).
1
Set the DVM to the 250 volt range.
2
Carefully measure the voltage between the hot and neutral side of the receptacle. The neutral wire
is white, the hot wire is black.
3
Verify the meter reads 106 to 128 VAC. If not, have a qualified electrician correct the problem.
4
Measure the voltage between the neutral and ground side of the receptacle. The ground wire is
green.
5
Verify the meter reads 0 VAC. If not, have a qualified electrician correct the problem.
6
Set all cabinet power modules OFF. Plug the AC power cable into the receptacle.
Return to Task List
Connect RPO
cable here (J21)
Connect external
alarm cable here
(J18)
Carrier
circuit
breakers
psdf002 CJL 081596
External
alarm cable
Pin 6 (-RPO)
Pin 2 (+RPO)
Содержание MCC1
Страница 38: ...Upgrades to Avaya Commnication Manager Made Easy Before you start 38 SI Installation and Upgrades June 2004 ...
Страница 326: ...Installation for MCC1 Multicarrier Cabinets Made Easy 326 SI Installation and Upgrades June 2004 ...
Страница 362: ... Single Carrier Cabinets Made Easy 362 SI Installation and Upgrades June 2004 ...
Страница 498: ...Test the System LED Indicators 498 SI Installation and Upgrades June 2004 ...
Страница 650: ...Add IP Solutions Task list Upgrade a TN802 to a TN802B 650 SI Installation and Upgrades June 2004 ...
Страница 692: ...Install and Administer Trunks Add TN1654 DS1 Converter r only 692 SI Installation and Upgrades June 2004 ...
Страница 770: ...Connecting and Handling Fiber Optic Cables Cleaning Fiber Optic Cables 770 SI Installation and Upgrades June 2004 ...
Страница 784: ...Connector and Cable Diagrams Pinout Charts DS1 Interface Cable H600 307 784 SI Installation and Upgrades June 2004 ...
Страница 792: ...UPS Installation for SCC1 EPN A Carrier Cabinet Task List Install UPS 792 SI Installation and Upgrades June 2004 ...