Addr.
Parameter
C
Setting Options
Default Setting
General
_:8341:1
Inverse-T 1:Mode
•
off
•
on
•
test
off
_:8341:2
Inverse-T 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:8341:111
Inverse-T 1:Directional
mode
•
forward
•
reverse
forward
_:8341:11
Inverse-T 1:1-pole
operate allowed
•
no
•
yes
no
_:8341:8
Inverse-T 1:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:8341:113
Inverse-T 1:Non-direc-
tional pickup
•
no
•
at volt.< & mem.empty
at volt.< &
mem.empty
_:8341:110
Inverse-T 1:Directional
comparison
•
no
•
yes
no
_:8341:112
Inverse-T 1:Release via
input signal
•
no
•
yes
no
_:8341:10
Inverse-T 1:Blk. by
meas.-volt. failure
•
no
•
yes
yes
_:8341:26
Inverse-T 1:Dynamic
settings
•
no
•
yes
no
_:8341:27
Inverse-T 1:Blk. w. inrush
curr. detect.
•
no
•
yes
no
_:8341:3
Inverse-T 1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A
7.50 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.500 A
5 A @ 50 Irated
0.15 A to 175.00 A
7.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.500 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
7.500 A
_:8341:130
Inverse-T 1:Type of char-
acter. curve
_:8341:114
Inverse-T 1:Min. time of
the curve
0.00 s to 1.00 s
0.00 s
_:8341:131
Inverse-T 1:Reset
•
instantaneous
•
disk emulation
disk emulation
_:8341:101
Inverse-T 1:Time dial
0.05 to 15.00
1.00
_:8341:115
Inverse-T 1:Additional
time delay
0.00 s to 60.00 s
0.00 s
Dyn.s: AR off/n.rdy
_:8341:28
Inverse-T 1:Effect. by AR
off/n.ready
•
no
•
yes
no
_:8341:35
Inverse-T 1:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:8341:29
Inverse-T 1:Effected by
AR cycle 1
•
no
•
yes
no
_:8341:36
Inverse-T 1:Stage
blocked
•
no
•
yes
no
Protection and Automation Functions
7.6 Directional Overcurrent Protection, Phases
686
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...