[loaussch-180912-01.tif, 1, en_US]
Figure 5-38
Tripping, Opening, and Closing the Circuit Breaker
Table 5-7
Description of the Output Signals
Signal
Description
Routing Options
Trip/open cmd. 3-
pole
This signal executes all 3-pole tripping and opening oper-
ations.
The
Output time
parameter affects the signal.
The signal is pending for the duration of this period, with
the following exceptions:
•
Only when switched off by the control: The signal is
canceled before expiration of the period if the auxil-
iary contacts report that the circuit breaker is open
before expiration of the period.
•
Only in the event of protection tripping: The signal
remains active as long as the trip command is still
active after expiration of the period (see also
).
•
Only in the event of protection tripping: With the
routing option Only saved in the event of tripping,
the signal remains pending until it is acknowledged
manually. This only applies for protection tripping.
•
Unlatched
•
Only saved in the
event of protection
tripping (not when
opened)
Trip only pole A
This signal only executes 1-pole tripping for phase A. If 3-
pole tripping occurs while a 1-pole trip signal is active,
the 1-pole signal is canceled.
The signal is active for as long as the trip command is
active, but at least for the duration of the output time.
Normal routing
Trip only pole B
This signal only executes 1-pole tripping for phase B. If 3-
pole tripping occurs while a 1-pole trip signal is active,
the 1-pole signal is canceled.
The signal is active for as long as the trip command is
active, but at least for the duration of the output time.
Normal routing
Trip only pole C
This signal only executes 1-pole tripping for phase C. If 3-
pole tripping occurs while a 1-pole trip signal is active,
the 1-pole signal is canceled.
The signal is active for as long as the trip command is
active, but at least for the duration of the output time.
Normal routing
Function-Group Types
5.6 Function-Group Type Circuit Breaker, 1-/3-Pole
SIPROTEC 5, High-Voltage Bay Controller, Manual
237
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...