Parameter: Rated current
•
Default setting
(_:9421:101) Rated current
=
1000 A
The
(_:9421:101) Rated current
parameter is used to set the primary rated current of the protected
object. The
(_:9421:101) Rated current
specified here is the reference value for the percentage-meas-
ured values and setting values made in percentages.
Parameter: Rated voltage
•
Default setting
(_:9421:102) Rated voltage
=
400.00 kV
With the
Rated voltage
parameter, you set the primary rated voltage of the protected object. The
Rated
voltage
set here is the reference value for all voltage-related percentage values in the Circuit-breaker func-
tion group.
If you connect the Voltage-current 1-phase function group with the 1-phase measuring point, the following
applies:
•
With connection type V
AB
, V
BC
, V
CB
, or V
N
, you set the
Rated voltage
parameter as the phase-to-phase
voltage.
•
With the connection type V
A
, V
B
, V
C
, or V
N (broken-delta winding)
, you set the
Rated voltage
parameter as the
phase-to-ground voltage.
•
With the connection type V
X
, you set the
Rated voltage
parameter as either the phase-to-phase
voltage or the phase-to-ground voltage
Parameter: P, Q sign
•
Default setting
(_:9421:150) P, Q sign
=
not reversed
The power values are set at the factory so that power in the direction of the protected object is considered
positive. You can also define the power output by the protected object as positive. With the
P, Q sign
parameter, you can invert the signs of active and reactive power. This inversion has no effect on the protec-
tion functions.
Write-Protected Settings
The settings listed here are used primarily for understanding during configuration of the function groups. They
are calculated on the basis of other settings and cannot be directly changed.
Addr.
Parameter
C
Setting Options
Default Setting
Rated values
_:9421:103
General:Rated apparent
power
-1.00 MVA to -1.00 MVA
0.00 MVA
Power-system data
_:9421:214
General:M I-1ph uses
MeasP with ID
0 to 100
0
_:9421:223
General:CT mismatch M
I-1ph
0.00 to 100.00
0.00
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Rated values
_:9421:101
General:Rated current
1 A to 100 000 A
1000 A
_:9421:102
General:Rated voltage
0.20 kV to 1200.00 kV
400.00 kV
5.3.4
5.3.5
Function-Group Types
5.3 Function-Group Type Voltage/current 1-Phase
204
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...