Addr.
Parameter
C
Setting Options
Default Setting
_:4861:8
Definite-T 1:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:4861:104
Definite-T 1:Directional
comparison
•
no
•
yes
no
_:4861:106
Definite-T 1:Release via
input signal
•
no
•
yes
no
_:4861:10
Definite-T 1:Blk. by
meas.-volt. failure
•
no
•
yes
yes
_:4861:26
Definite-T 1:Dynamic
settings
•
no
•
yes
no
_:4861:27
Definite-T 1:Blk. w.
inrush curr. detect.
•
no
•
yes
no
_:4861:3
Definite-T 1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:4861:4
Definite-T 1:Dropout
ratio
0.90 to 0.99
0.95
_:4861:101
Definite-T 1:Dropout
delay
0.00 s to 60.00 s
0.00 s
_:4861:6
Definite-T 1:Operate
delay
0.00 s to 60.00 s
0.30 s
Dyn.s: AR off/n.rdy
_:4861:28
Definite-T 1:Effect. by AR
off/n.ready
•
no
•
yes
no
_:4861:35
Definite-T 1:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:4861:29
Definite-T 1:Effected by
AR cycle 1
•
no
•
yes
no
_:4861:36
Definite-T 1:Stage
blocked
•
no
•
yes
no
_:4861:14
Definite-T 1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:4861:20
Definite-T 1:Operate
delay
0.00 s to 60.00 s
0.30 s
Dyn.set: AR cycle 2
_:4861:30
Definite-T 1:Effected by
AR cycle 2
•
no
•
yes
no
_:4861:37
Definite-T 1:Stage
blocked
•
no
•
yes
no
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
716
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...