With the
Threshold light
parameter, you set the light sensitivity. If you set
Threshold light
to a
smaller value, the sensitivity increases. If you set
Threshold light
to a higher value, the sensitivity
decreases. If the sensors even pick up in case of a switching arc of the circuit breaker, set the
Threshold
light
parameter to a higher value.
Siemens recommends the default settings for point or line sensors.
Set the parameter
Threshold light
manually only if you have special default settings for light sensitivity.
Parameter: Channel
•
Default setting
(_:14551:10) Channel
=
No channel is selected
With the
Channel
parameter, you select which sensor channel the stage uses.
If the Arc protection function has several stages, a different channel must be selected for each stage.
For parameter
Channel
, the selection texts are identical to the name of the arc-protection module and its
channels.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:2311:3
General:Threshold I>
1 A @ 100 Irated 0.030 A to 35.000 A
2.000 A
5 A @ 100 Irated 0.15 A to 175.00 A
10.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
2.000 A
5 A @ 50 Irated
0.15 A to 175.00 A
10.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
2.000 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
10.000 A
_:2311:4
General:Threshold 3I0>
1 A @ 100 Irated 0.030 A to 35.000 A
1.000 A
5 A @ 100 Irated 0.15 A to 175.00 A
5.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.000 A
5 A @ 50 Irated
0.15 A to 175.00 A
5.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.000 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
5.000 A
Stage 1
_:14551:1
Stage 1:Mode
•
off
•
on
•
test
off
_:14551:2
Stage 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:14551:9
Stage 1:External trip
initiation
•
no
•
current
•
light
no
_:14551:8
Stage 1:Operating mode
•
light only
•
current and light
current and light
_:14551:11
Stage 1:Sensor
•
point sensor
•
line sensor
•
custom
point sensor
_:14551:7
Stage 1:Threshold light
-34.00 dB to -10.00 dB
-20.00 dB
_:14551:10
Stage 1:Channel
Setting options depend on
configuration
7.29.6
Protection and Automation Functions
7.29 Arc Protection
SIPROTEC 5, High-Voltage Bay Controller, Manual
917
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...