Parameter:
Threshold
•
Default setting
(_:104) Threshold
=
1000
You use the
Threshold
parameter to define the threshold of residual switching cycles with rated normal
current. A warning signal is generated when the statistic is less than the
Threshold
.
Example
Here is an example that shows you how to set the
Threshold
parameter. Assuming a circuit breaker with the
same technical data as provided in the example for residual switching cycles, 50 breaking operations with
rated short-circuit breaking current are permitted.
A warning signal should be issued when the number of possible breaking operations with rated short-circuit
breaking current is less than 3. For that condition, you set the
Threshold
value based on the following calcu-
lation:
[FoCBW2P4-301012-01.tif, 1, en_US]
Settings
Addr.
Parameter
C
Setting Options
Default Setting
2P-method
_:1
2P-method:Mode
•
off
•
on
•
test
off
_:101
2P-method:Switching
cycles at Ir
100 to 1000000
10000
_:102
2P-method:Rated short-
circ.cur. Isc
10 A to 100000 A
25000 A
_:103
2P-method:Switching
cycles at Isc
1 to 1000
50
_:104
2P-method:Threshold
0 to 10000000
100
Information List
No.
Information
Data Class
(Type)
Type
2P-method
_:54
2P-method:Inactive
SPS
O
_:52
2P-method:Behavior
ENS
O
_:53
2P-method:Health
ENS
O
_:301
2P-method:Endur.A
INS
O
_:302
2P-method:Endur.B
INS
O
_:303
2P-method:Endur.C
INS
O
_:304
2P-method:Warning
ACT
O
9.6.5.3
9.6.5.4
Measured Values, Energy Values, and Supervision of the Primary System
9.6 Circuit-Breaker Wear Monitoring
SIPROTEC 5, High-Voltage Bay Controller, Manual
1031
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...