Displayed Information
Explanation
Fault distance
Display of the measured fault-location distance.
Acknowledgement of the Spontaneous Fault Display on the Device
After faults, the last occurred fault is always displayed to you. In cases where more than one circuit breaker is
configured, several stored fault displays can be present after faults, with the latest being displayed. These
displays remain stored in the device until they are manually acknowledged or reset by LED reset.
Figure 3-25
Spontaneous Fault Display on the Device
Method 1: Manual acknowledgement
•
Press the softkey button Quit in the base bar of the display. The display is irretrievably closed. Repeat this
step until no spontaneous fault display appears anymore.
•
After completion of all confirmations the last display view is showed before the faults.
Method 2: Acknowledgement via LED reset
•
An LED reset (device) causes the reset of all stored LEDs and binary output contacts of the device and also
to the confirmation of all fault displays stored in the display.
You can find more details on the topic of LED reset in chapter
3.1.9 Stored Indications in the SIPROTEC 5
Stored Indications in the SIPROTEC 5 Device
In your SIPROTEC 5 device, you can also configure indications as stored. This type of configuration can be
used for LEDs as well as for output contacts. The configured output (LED or contact) is activated until it is
acknowledged. Acknowledgment occurs via:
•
On-site operation panel
•
DIGSI 5
•
Binary input
•
Protocol of substation automation technology
Configuration of Stored Indications with DIGSI 5
In the Information Routing of each device set up in DIGSI 5, you can route binary signals, among others, to
LEDs and output contacts.
•
To do this, proceed in the project tree to:
Project → Device → Information routing
•
Right-click the routing field of your binary indication in the desired LED or binary output column in the
routing range of the targets.
3.1.9
System Functions
3.1 Indications
SIPROTEC 5, High-Voltage Bay Controller, Manual
71
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...