No.
Information
Data Class
(Type)
Type
_:5071:317
Synchrocheck 1:V dif.too large(V2>V1)
SPS
O
_:5071:318
Synchrocheck 1:V dif.too large(V2<V1)
SPS
O
_:5071:319
Synchrocheck 1:f dif.too large(f2>f1)
SPS
O
_:5071:320
Synchrocheck 1:f dif.too large(f2<f1)
SPS
O
_:5071:329
Synchrocheck 1:dfdiff/dt too large
SPS
O
_:5071:321
Synchrocheck 1:α dif.too large(α2>α1)
SPS
O
_:5071:322
Synchrocheck 1:α dif.too large(α2<α1)
SPS
O
_:5071:304
Synchrocheck 1:Max. time exceeded
SPS
O
_:5071:323
Synchrocheck 1:Setting error
SPS
O
Stage Synchronous/Asynchronous
Description
A distinction according to synchronous and asynchronous systems can be made with this type of stage.
If galvanically coupled systems are switched in parallel, synchronous systems are present. A typical character-
istic for synchronous systems is equality of frequency (Δf ≈ 0). If the frequency difference falls below the
setting value of the
f-threshold ASYN<->SYN
parameter, synchronous systems are to be assumed. If the
frequency difference exceeds the setting value of the
f-threshold ASYN<->SYN
parameter, asynchronous
systems are to be assumed. This status occurs in galvanically isolated systems, for example.
Both states have their own operating mode with its own closing conditions. Both operating modes can be
switched on and off separately (parameter
Sync. operating mode
and
Async. operating mode
). The
following combinations result from this:
Sync. operating mode Async. operating
mode
Functionality
on
on
If the frequency difference is below the threshold
value set
f-threshold ASYN<->SYN
the oper-
ating mode synchronous is active. In other cases,
the operating mode asynchronous is active.
off
on
Regardless of the frequency difference and the
threshold value
f-threshold ASYN<->SYN
the
operating mode is exclusively active asynchro-
nously.
on
off
If the frequency difference is below the threshold
value set
f-threshold ASYN<->SYN
, the oper-
ating mode synchronous is active. In other cases,
the stage is inactive, i.e. a switching release
cannot be issued.
off
off
Both operating modes are deactivated. No activa-
tion release can be be given via these operating
modes either.
6.4.8
6.4.8.1
Control Functions
6.4 Synchronization Function
380
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...