Notes for Optional Input Interconnections
You have the option of connecting the input signals
>Close cmd. released
and
>In progress
. If you
omit these interconnections, observe the following instructions:
Input
>Close cmd. released
:
If you do not interconnect the input signal
>Close cmd. released
, the execution of a circuit-breaker close
command with synchronization requirement is confirmed directly (execution successful: OPR+), as soon as the
output signal
Start syn. process
is set. In this case, the
(_:109) Max.durat. sync.process
setting has no meaning. If you use a control model with feedback monitoring, consider that the feedback
monitoring will start immediately when the
Start syn. process
signal is tripped. The
(_:4201:103)
Feedback monitoring time
setting must therefore be set higher than the maximum synchronization
time of the external synchronization device plus the circuit-breaker closing time. If
>Close cmd. released
is not routed, the output
Start/stop syn. proc.
is not set.
Input
>In progress
:
The interconnection of the input signal
>In progress
is intended to check whether the synchronization
device has received the
Start syn. process
signal. If you do not interconnect this input signal and the
external synchronization device rejects a start command, the negative acknowledgment of the circuit-breaker
close command does not occur until the maximum synchronization time (parameter
(_:109) Max.durat.
sync.process
) has expired.
Input
>Op. mode 'dir.cls.cmd'
:
In case of a failure of the external synchronization device, you can also close the circuit breaker directly
without considering the synchronization conditions. To do this, activate the input signal
>Op. mode
'dir.cls.cmd'
or the parameter
(_:110) Direct close command
. The close command is then issued
directly by the bay controller.
Application and Setting Notes (External Synchronization)
Parameter:
Mode
•
Default setting
(_:1) Mode
=
on
With the
Mode
parameter, you switch the external synchronization function on or off. If you set the
Mode
parameter to
off
, a circuit-breaker close command with synchronization requirement is rejected.
Parameter:
Max.durat. sync.process
•
Default setting
(_:109) Max.durat. sync.process
=
30 s
The
Max.durat. sync.process
parameter defines the maximum synchronization time. The time starts
when the External synchronization function block sends a close command to the external synchronization
device. The command must be executed within this time. If the close command is not executed within this
time, the External synchronization function block sends a command to cancel closing to the external
synchronization device.
Parameter:
Direct close command
•
Default setting
(_:110) Direct close command
=
no
In case of a failure of the external synchronization device the
Direct close command
parameter is used to
close the circuit breaker directly without considering the synchronization conditions. If the parameter is acti-
vated a close command with synchronization requirement will not be transmitted to the external synchroniza-
tion device, but directly carried out by the bay controller.
6.4.14.2
Control Functions
6.4 Synchronization Function
SIPROTEC 5, High-Voltage Bay Controller, Manual
417
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...