Parameter: Start from idle state allow.
This parameter is only important and can be set if you use the automatic reclosing function in an operating
mode
with action time
.
•
Default setting
(_:6571:102) Start from idle state allow.
=
yes
With the parameter
Start from idle state allow.
you can determine whether the action time of this
automatic reclosing cycle is started, if the automatic reclosing function is in idle state during with incoming
general pickup. Please set the parameter always to
yes
, if the automatic reclosing function is configured for
only 1 cycle. If several cycles are configured, you can control the effectiveness of the automatic reclosing
cycles with this parameter and various action times.
Detailed information about the functionality can be found in Chapters
7.2.4.6 Cycle Control with Operating
Mode 1: With Tripping/With Action Time
7.2.4.7 Cycle Control with Operating Mode 2: With Pickup/With
Parameter: Action time
This parameter is only important and can be set if you use the automatic reclosing function in an operating
mode
with action time
.
•
Default setting
(_:6571:103) Action time
=
0.2 s
With this parameter
Action time
you can determine, within which time frame the trip command must
appear, in order to start the automatic reclosing function. If the trip command occurs only after the action
time has expired, automatic reclosing does not occur within the active automatic reclosing cycle.
You can find detailed information about the functionality in
Chapters
7.2.4.6 Cycle Control with Operating Mode 1: With Tripping/With Action Time
Control with Operating Mode 2: With Pickup/With Action Time
Parameter: Dead time aft. 3-pole trip
This parameter is only important and can be set if you use the automatic reclosing function in an operating
mode
with tripping
.
•
Default setting
(_:6571:108) Dead time aft. 3-pole trip
=
0.5 s
With this parameter
Dead time aft. 3-pole trip
, you can determine after which dead time the auto-
matic reclosing function will be executed. After a 3-pole trip of the circuit breaker, the system stability is
priority. Since the switched off line cannot develop synchronizing forces, only a short dead time is permitted in
most cases. The usual duration is 0.3 s to 0.6 s. A longer period can be tolerated if a synchrocheck is carried
out prior to reclosing. Longer 3-pole dead times are also possible in radial systems.
Parameter: Dead time aft.1ph. pickup, Dead time aft.2ph. pickup, Dead time aft.3ph. pickup
This parameter is only important and can be set if you use the automatic reclosing function in an operating
mode
with pickup
.
•
Default setting
(_:6571:104) Dead time aft.1ph. pickup
=
1.2 s
•
Default setting
(_:6571:105) Dead time aft.2ph. pickup
=
1.2 s
•
Default setting
(_:6571:106) Dead time aft.3ph. pickup
=
0.5 s
With the 3 dead-time parameters, you can determine after which dead time the automatic reclosing function
will be executed. Please set the times as desired for the respective type of short circuit.
•
The parameter
Dead time aft.1ph. pickup
applies to dead times after 1-phase short circuits and
the following protection tripping: A, B, C, or A-Gnd, B-Gnd, C-Gnd
•
The parameter
Dead time aft.2ph. pickup
applies to dead times after 2-phase short circuits and
the following protection tripping: A-B, B-C, C-A, or A-B-gnd, B-C-gnd, C-A-gnd
•
The parameter
Dead time aft.3ph. pickup
applies to dead times after 3-phase short circuits and
the following protection tripping: A-B-C or A-B-C-Gnd
Protection and Automation Functions
7.2 Automatic Reclosing Function
592
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...