Table 6-26
Routing of the Binary Inputs (Tap-Coding Type BCD)
Example
BI1
BI2
BI3
BI4
BI5
BI6
BI7
Tap changer
X
X
X
X
X
X
X
Meaning
BCD 1
BCD 2
BCD 4
BCD 8
BCD 10
BCD 20
Moving
contact
Tap = 21
1
0
0
0
0
1
With 6 binary inputs, a maximum of 39 tap positions can be mapped with the tap-coding type of BCD. This
results in the number of tap positions from 1 to 39. If all routed binary inputs indicate 0, this is detected as tap
0. The 7 binary inputs must be numbered sequentially, for example, BI 1, BI 2, BI 3, BI 4, BI 5, BI 6, and BI 7 for
the moving contact.
Tap-coding type:
BCD
Number of tap positions:
39
Number of bits f. tap code:
7
Tap-display offset:
0
Moving contact (highest binary input):
Yes
Individual Tap-Coding Type (table)
With the
table
parameter setting, you can specify an individual
Tap-coding type
.
In the
Representation of encoding
section, select the number system in which your code table entries
will take place, alternatively:
•
Binary (2 characters)
•
Octal (8 characters)
•
Decimal (10 characters)
•
Hexadecimal (16 characters)
The selected option is valid for all inputs in the
Encoding
column.
If you change the number system and there are already entries in this column, these will be converted to the
new number system. The selection area gets visible as soon as you have selected the
table
setting in the
Tap-coding type
list box.
[sccotabi-111016-01, 1, en_US]
Figure 6-114
Code Table for the Tap-Code Type table
Control Functions
6.8 Transformer Tap Changers
SIPROTEC 5, High-Voltage Bay Controller, Manual
445
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...