Other Functions
Signal Filtering and Chatter Blocking for Input Signals
Input signals can be filtered to suppress brief changes at the binary input. Chatter blocking can be used to
prevent continuously changing indications from clogging the event list. After an adjustable number of
changes, the indication is blocked for a certain period.
The settings for indication filtering can be found at the individual signals. The next figure shows the settings
using the example of a controllable (circuit-breaker switch position).
i
i
NOTE
For the circuit breaker or the disconnector, the settings of the software filter for spontaneous position
changes are available only in the Control/Command with feedback function block. These settings are not
available in the Circuit breaker or Disconnector function blocks since these function blocks contain the
actual unfiltered position of the switch in the bay.
[sclposi-260116, 1, en_US]
Figure 3-78
Settings for Circuit-Breaker Switch Position
The setting range for the
Software filtering time
parameter ranges from 0 ms to 86 400 000 ms (1
day) in ms increments. The
Retrigger filter
check box can be used to select whether the software filter
should be restarted by a change from 1 to 0 and back. When activated, the
Indication timestamp
before filtering
check box back dates the time stamp by the set software filtering time and the fixed
hardware filtering time. In this case, the time stamp corresponds to the actual status change of the signal. If
you activate the
Suppress intermediate position
check box, the intermediate position is suppressed
for the duration of this software filter time.
With the parameter
Spontaneous position changes filtered by
, you set how such position
changes are to be filtered. Spontaneous position changes are caused by external switching commands, for
3.8
3.8.1
System Functions
3.8 Other Functions
SIPROTEC 5, High-Voltage Bay Controller, Manual
143
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...