Settings
Addr.
Parameter
C
Setting Options
Default Setting
Cold-load PU
_:1
Cold-load PU:Mode
•
off
•
on
•
test
off
_:101
Cold-load PU:Operating
mode
•
I open
•
CB and I open
I open
_:102
Cold-load PU:Dropout
threshold current
1 A @ 100 Irated 0.030 A to 10.000 A
1.000 A
5 A @ 100 Irated 0.15 A to 50.00 A
5.00 A
1 A @ 50 Irated
0.030 A to 10.000 A
1.000 A
5 A @ 50 Irated
0.15 A to 50.00 A
5.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.000 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
5.000 A
_:103
Cold-load PU:Dropout
delay curr.crit.
1sto600 s
600s
_:104
Cold-load PU:Dropout
delay CB closed
1 s to 21600 s
3600 s
_:105
Cold-load PU:Min. CB-
open time
0 s to 21600 s
3600 s
Information List
No.
Information
Data Class
(Type)
Type
Cold-load PU
_:81
Cold-load PU:>Block stage
SPS
I
_:500
Cold-load PU:>Block fast dropout
SPS
I
_:501
Cold-load PU:>Activate cold-load
SPS
I
_:54
Cold-load PU:Inactive
SPS
O
_:52
Cold-load PU:Behavior
ENS
O
_:53
Cold-load PU:Health
ENS
O
_:300
Cold-load PU:Cold-load pickup
SPS
O
5.8.11
5.8.12
Function-Group Types
5.8 Process Monitor
SIPROTEC 5, High-Voltage Bay Controller, Manual
299
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...