Parameter: Dropout ratio
•
Recommended setting value
(_:211:4) Dropout ratio
=
0.95
The default value of
0.95
is appropriate for most applications. To achieve high measurement precision, the
Dropout ratio
can be reduced, to 0.98, for example.
General Notes
If the overvoltage is high, the first stage can trip with a short time delay. If overvoltages are lower, the second
stage can either only signal the threshold value violation (see Operation as monitoring function) or trip with a
longer delay to allow the voltage controller to regulate the voltage back into the nominal range.
Operation as Supervision Function
If you want the tripping stage to have a reporting effect only, generation of the operate indication and fault
logging can be disabled via the
Operate & flt.rec. blocked
parameter.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Stage 1
_:211:1
Stage 1:Mode
•
off
•
on
•
test
off
_:211:2
Stage 1:Operate & flt.rec.
blocked
•
no
•
yes
no
_:211:3
Stage 1:Threshold
0.300 V to 200.000 V
65.000 V
_:211:4
Stage 1:Dropout ratio
0.90 to 0.99
0.95
_:211:6
Stage 1:Operate delay
0.00 s to 60.00 s
3.00 s
Stage 2
_:212:1
Stage 2:Mode
•
off
•
on
•
test
off
_:212:2
Stage 2:Operate & flt.rec.
blocked
•
no
•
yes
no
_:212:3
Stage 2:Threshold
0.300 V to 200.000 V
75.000 V
_:212:4
Stage 2:Dropout ratio
0.90 to 0.99
0.95
_:212:6
Stage 2:Operate delay
0.00 s to 60.00 s
0.50 s
Information List
No.
Information
Data Class
(Type)
Type
Group indicat.
_:4501:55
Group indicat.:Pickup
ACD
O
_:4501:57
Group indicat.:Operate
ACT
O
Stage 1
_:211:81
Stage 1:>Block stage
SPS
I
_:211:54
Stage 1:Inactive
SPS
O
_:211:52
Stage 1:Behavior
ENS
O
_:211:53
Stage 1:Health
ENS
O
_:211:55
Stage 1:Pickup
ACD
O
7.14.5
7.14.6
Protection and Automation Functions
7.14 Overvoltage Protection with Positive-Sequence Voltage
SIPROTEC 5, High-Voltage Bay Controller, Manual
797
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...