NOTE
If the Arc protection function operates via the
External trip initiation
, only 3 optical point
sensors are required per feeder protection device in order to detect the arcs (only one arc-protection
module).
The number of GOOSE messages is not limited. Therefore, the number of feeders is not limited, and the
protection of complex systems is feasible.
Application and Setting Notes
General Notes:
•
Install the optical point sensors in the busbar compartment, the circuit-breaker compartment, and the
cable-connection compartment of the feeders and the infeed to the respective protection devices.
•
Arcs in the busbar compartment and the circuit-breaker compartment of the feeders must be switched
off by the protection device in the infeed. To do this, the protection devices in the feeder device must
send the indication
Light detected
to the infeed device. Use the binary inputs/outputs, a protection
interface, or IEC 61850 GOOSE.
The protection device in the infeed evaluates the current. If the measured current exceeds the
Threshold I>
and/or
Threshold 3I0>
threshold values, the protection device in the infeed switches
off faults on the busbar and the circuit-breaker compartment of the feeders.
Connect the signals over 4 stages, using the external trip initiation or a CFC chart.
•
Arcs in the cable-connection compartment of the feeders are switched off locally. The protection device
in the infeed evaluates the current. If the measured current exceeds the threshold values
Threshold
I>
and/or
Threshold 3I0>
, the
Current detected
indication is sent to the protection devices in
the feeders. If, at the same time, an optical sensor in a cable-connection compartment detects light, the
protection device trips in the corresponding feeder.
Setting Notes for the Protection Device in Feeder 1
The Arc protection function operates with 3 stages.
Stage 1 and 2 (supervision of busbar compartment and circuit-breaker compartment):
Set the parameters of the stages as follows:
•
Parameter:
Operating mode
=
light only
•
Parameter:
Sensor
=
point sensor
•
Parameter:
External trip initiation
=
no
•
Parameter:
Operate & flt.rec. blocked
=
yes
•
Parameter:
Channel
= (Stage 1) → busbar-compartment supervision in feeder 1
Parameter:
Channel
= (Stage 2) → circuit-breaker compartment supervision in feeder 1
Stage 3 (supervision of cable-connection compartment):
Set the parameters of the stage as follows:
•
Parameter:
Operating mode
=
current and light
•
Parameter:
Sensor
=
point sensor
•
Parameter:
External trip initiation
=
current
The protection device in the infeed evaluates the current. If the measured current exceeds the threshold
values
Threshold I>
and/or
Threshold 3I0>
, the protection device in the infeed returns the indica-
tion
Current detected
to the protection device in the feeder.
Only if the indication in the feeder device
Current detected
is connected with the signal
>External
current
an external trip initiation for this stage is effective.
7.29.10.2
Protection and Automation Functions
7.29 Arc Protection
926
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...