[scawe6md-160212-01.tif, 1, en_US]
Figure 7-26
Configuration of the Protection Functions for Starting and Blocking the Automatic Reclosing
Function in DIGSI 5
If a protection function or the stage of a protection function is connected with the AREC through the matrix,
this means that the respective pickup and operate indications are forwarded to the AREC.
The links can be conducted separately
•
For starting the automatic reclosing function and
•
For the blocking of the automatic reclosing function
The Automatic reclosing function also has the corresponding binary inputs and binary outputs through which
the external protection devices can be connected to the internal Automatic reclosing function.
Cyclic Automatic Reclosing Function
Operating Modes for Cyclic Automatic Reclosing Function
For the cyclic automatic reclosing function, there are 4 operating modes, from which one can be selected for
the parameterization (parameter
(_:6601:101) 79 operating mode
).
The selection of the operating mode is dependent on the tripping behavior of the protection functions and the
circuit breaker.
For applications with 3-pole tripping, all 4 operating modes are available.
•
Operating mode 1:
with op., with act. time
•
Operating mode 2:
w.pickup, w. action time
•
Operating mode 3:
with op., w/o act. time
•
Operating mode 4:
w.pickup, w/o act. time
Operating Mode 1: with op., with act. time
The operating mode
with op., with act. time
allows different automatic reclosing cycles depending
on the tripping type and operate time of the protection function(s). With this operating mode, the automatic
7.2.4
7.2.4.1
Protection and Automation Functions
7.2 Automatic Reclosing Function
546
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...