Parameter: Release threshold
•
Recommended setting value
(_:101) Release threshold
=
50 V
With the
Release threshold
parameter you set the lower limit of the maximum phase-to-phase voltage
(V
max
). Siemens recommends using the default setting.
Parameter: Delay failure indication
•
Recommended setting value
(_:6) Delay failure indication
=
5.00 s
Set the
Delay failure indication
parameter so that overfunctions due to disturbing influences (such as
switching operations) are avoided. Siemens recommends using the default setting.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Supv. balan. V
_:1
Supv. balan. V:Mode
•
off
•
on
•
test
off
_:101
Supv. balan. V:Release
threshold
0.300 V to 170.000 V
50.000 V
_:102
Supv. balan. V:Threshold
min/max
0.58 to 0.95
0.75
_:6
Supv. balan. V:Delay
failure indication
0.00 sto 100.00 s
5.00 s
Information List
No.
Information
Data Class
(Type)
Type
Supv. balan. V
_:82
Supv. balan. V:>Block function
SPS
I
_:54
Supv. balan. V:Inactive
SPS
O
_:52
Supv. balan. V:Behavior
ENS
O
_:53
Supv. balan. V:Health
ENS
O
_:71
Supv. balan. V:Failure
SPS
O
Voltage-Sum Supervision
Overview of Functions
In healthy system operation, the sum of all voltages at one measuring point must be approximately 0. The
Voltage-sum supervision monitors the sum of all voltages of one measuring point in the secondary circuit. It
detects connection errors during commissioning or short circuits and interruptions in the secondary circuit. For
summation of the voltages, the 3 phase-to-ground voltages and the residual voltage (da-dn - voltage of an
open-circuited delta winding) are required.
The voltage measurement is based on the RMS values of the fundamental component.
i
i
NOTE
For the Voltage-sum supervision, the externally generated residual voltage must be connected to the 4th
voltage measuring input.
For the Voltage-sum supervision to work correctly, the
Matching ratio Vph / VN
parameter must be
set accordingly.
8.3.5.5
8.3.5.6
8.3.6
8.3.6.1
Supervision Functions
8.3 Supervision of the Secondary System
954
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...