Addr.
Parameter
C
Setting Options
Default Setting
_:110
External sync.:Direct
close command
•
0
•
1
false
Information List
No.
Information
Data Class
(Type)
Type
External sync.
_:506
External sync.:>Synch. device ready
SPS
I
_:508
External sync.:>In progress
SPS
I
_:507
External sync.:>Close cmd. released
SPS
I
_:509
External sync.:>Op. mode 'dir.cls.cmd'
SPS
I
_:52
External sync.:Behavior
ENS
O
_:54
External sync.:Health
ENS
O
_:55
External sync.:Start syn. process
SPS
O
_:56
External sync.:Stop syn. process
SPS
O
_:57
External sync.:Start/stop syn. proc.
SPS
O
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:2311:127
General:Angle adjust.
(transform.)
-179.0 ° to 180.0 °
0.0 °
General
_:5071:1
Synchrocheck 1:Mode
•
off
•
on
•
test
off
_:5071:101
Synchrocheck 1:Min. oper-
ating limit Vmin
0.300 V to 340.000 V
90.000 V
_:5071:102
Synchrocheck 1:Max.
operat. limit Vmax
0.300 V to 340.000 V
110.000 V
_:5071:110
Synchrocheck 1:Max.durat.
sync.process
0.00 s to 3600.00 s; ∞
30.00 s
_:5071:108
Synchrocheck 1:Direct close
command
•
no
•
yes
no
_:5071:126
Synchrocheck 1:Voltage
adjustment
0.500 to 2.000
1.000
De-en.gized switch.
_:5071:105
Synchrocheck 1:Close cmd.
at V1< & V2>
•
no
•
yes
no
_:5071:106
Synchrocheck 1:Close cmd.
at V1> & V2<
•
no
•
yes
no
_:5071:107
Synchrocheck 1:Close cmd.
at V1< & V2<
•
no
•
yes
no
_:5071:103
Synchrocheck 1:V1, V2
without voltage
0.300 V to 170.000 V
5.000 V
_:5071:104
Synchrocheck 1:V1, V2
with voltage
0.300 V to 340.000 V
80.000 V
6.4.14.4
6.4.15
Control Functions
6.4 Synchronization Function
420
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...