Phasor Measurement Unit (PMU)
Overview of Functions
A Phasor Measurement Unit (PMU) measures the phasor values of current and voltage. These values get a high
precision time stamp and together with the values of power frequency, power frequency change rate and
optional binary data that are also time stamped are transmitted to a central analysis station. The standardized
transmission protocol IEEEC 37.118 is used to do this.
Structure of the Function Group
The PMU function group is activated by selecting the protocol
IEEE C37.118PMU
on an Ethernet module
(electrical or optical). The PMU obtains the measured values from the measuring points and the precise time
from time synchronization. The time-stamped synchrophasors for current and voltage are formed from this
and transferred together with additional values via the communication module to a server (PDC, Phasor Data
Concentrator).
[dwstrpmu-250613-01.tif, 2, en_US]
Figure 9-2
Structure/Embedding of the Function
Function Description
The synchrophasors, sent from the PMU in a continuous data stream to a PDC, are provided with time stamps
and thus are comparable with the measured values of other PMUs. The power frequency, the power frequency
change rate and optional binary information are also transmitted as time-stamped measured values. There-
fore, you receive an overview of the transient processes in a distributed energy transfer system, for example
network fluctuations and compensating processes.
The following table shows the differences between the PMU measured values and the remaining measured
values of the device.
9.5
9.5.1
9.5.2
9.5.3
Measured Values, Energy Values, and Supervision of the Primary System
9.5 Phasor Measurement Unit (PMU)
1000
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...