Addr.
Parameter
C
Setting Options
Default Setting
_:13111:107
Channel 1:Range active
•
0
•
1
false
_:13111:104
Channel 1:Conversion
factor
1 to 1000000
100
_:13111:105
Channel 1:Upper limit
0.00 mA to 20.00 mA
20.00 mA
_:13111:109
Channel 1:Upper limit -
Sensor
-1000000 to 1000000
100
_:13111:106
Channel 1:Lower limit
0.00 mA to 20.00 mA
4.00 mA
_:13111:110
Channel 1:Lower limit -
Sensor
-1000000 to 1000000
100
Information List
No.
Information
Data Class
(Type)
Type
General
_:2311:53
General:Health
ENS
O
_:2311:56
General:Failure
SPS
O
Channel 1
_:13111:53
Channel 1:Health
ENS
O
_:13111:71
Channel 1:Failure
SPS
O
_:13111:301
Channel 1:20-mA output scale
MV
O
_:13111:302
Channel 1:20-mA output raw
MV
O
20-mA Unit Serial
Overview
The function 20-mA unit Serial:
•
Provides serial communications with a 20-mA unit via the Modbus protocol and records the values meas-
ured by the 20-mA unit
•
Transforms the measured 20-mA values into slowly changing process variables such as temperature or
gas pressure
•
Makes the recorded process tags available to CFC, GOOSE, protocols and the device display
•
Monitors communication with the 20-mA unit
The function 20-mA unit Serial is structured in the same way as the function 20-mA Unit Ether.. The mode of
operation is also identical. The only difference is that the measured values are transferred to the communica-
tion module via a serial connection instead of an Ethernet connection.
You can find more information in Chapter
5.7.3.2 Structure of the Function
.
Application and Setting Notes
Parameter: Port
•
Default setting
(_:2311:103) Port
=
Port J
With the
Port
setting, you specify the slot for the communication module that will be used for the connection
with an external 20-mA unit.
Parameter: Channel number
•
Default setting
(_:2311:105) Channel number
=
1
5.7.3.8
5.7.4
5.7.4.1
5.7.4.2
Function-Group Types
5.7 Function-Group Type Analog Units
262
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...