With all voltage controllers, approach a
minimum
tap position where the same no-load voltages result
everywhere, and repeat the following tests.
–
If the difference of the circulating reactive current control deviation ∣ΔV
actK
(n+1) - ΔV
actK
(n)∣ is
smaller than the set bandwidth, increase the parameter
Reactive I control factor
.
–
If the difference of the circulating reactive current control deviation∣ΔV
actK
(n+1) - ΔV
actK
(n)∣ is larger
than double the bandwidth, reduce the parameter
Reactive I control factor
.
•
Repeat this test for all voltage controllers.
•
With all voltage controllers, approach a
maximum
tap position where the same no-load voltages result
everywhere, and repeat the following tests.
–
If the difference of the circulating reactive current control deviation∣ΔV
actK
(n+1) - ΔV
actK
(n)∣ is
smaller than the set bandwidth, increase the parameter
Reactive I control factor
.
–
If the difference of the circulating reactive current control deviation∣ΔV
actK
(n+1) - ΔV
actK
(n)∣ is larger
than double the bandwidth, reduce the parameter
Reactive I control factor
.
•
Repeat this test for all voltage controllers.
Since the transformer reactance can change slightly with the tap position, the points with
maximum
and
minimum
tap position mentioned in the preceding section are used to check the stable control.
Checking the Tap Direction and the Set Bandwidth in Parallel Operation with the Master-Follower Method
The following prerequisites apply for the following test:
•
All transformers are switched on.
•
All transformers feed to the same busbar.
•
All voltage controllers are in parallel mode.
•
The Master device is in the
Manual
operating mode.
•
The Follower devices are in the
Auto
operating mode.
i
i
NOTE
Carry out these tests only at low load current.
The test sequence corresponds to the sequence under
Checking the Tap Direction and the Set Bandwidth,
.
•
In addition, test the manually updated tap position of the Follower devices.
If the current is measured on the involved voltage controllers, the line compensation or the circulating reactive
current blocking is activated, you must check the currents.
i
i
NOTE
If a circulating reactive current forms despite the same tap position, there is an error in the tap-position
assignment.
Functional Tests
10.10 Commissioning Hints for Voltage Control
1090
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...