Measured Value
With the
Measured value
parameter, you define whether the stage analyzes the phase-to-phase voltages
V
AB
, V
BC
, and V
CA
, or the phase-to-ground voltages V
A
, V
B
, and V
C
.
If the measured value is set to phase-to-phase, the function reports those measuring elements that have
picked up.
Pickup Mode
With the
Pickup mode
parameter, you define whether the stage picks up when there is a lower threshold-
value violation in one measuring element (
1 out of 3
) or when there is a lower threshold-value violation in
all 3 measuring elements (
3 out of 3
).
Pickup and Operate Curve
When the input voltage falls below the threshold value by a settable value
Pickup factor
, the stage picks
up and the inverse-time characteristic curve is processed. The operate delay starts. The operate delay is the
sum of inverse-time delay and additional time delay.
T
op
=T
Inv
+ T
add
Where:
T
op
Operate delay
T
Inv
Inverse-time delay
T
add
Additional time delay (Parameter
Additional time delay
)
After pickup the time value T
Inv
is calculated for every input voltage less than the dropout value. An integrator
accumulates the value 1/T
Inv
. Once the accumulated integral reaches the fixed value 1, the inverse-time delay
expires. The stage operates after the additional time delay.
The inverse-time delay is calculated with the following formula:
[fo_UVP3ph_inverse, 2, en_US]
Where
T
Inv
Inverse-time delay
T
p
Time multiplier (Parameter
Time dial
)
V
Measured undervoltage
V
Thresh
Threshold value (Parameter
Threshold
)
k
Curve constant k (Parameter
Charact. constant k
)
α
Curve constant α (Parameter
Charact. constant α
)
c
Curve constant c (Parameter
Charact. constant c
)
Protection and Automation Functions
7.16 Undervoltage Protection with 3-Phase Voltage
SIPROTEC 5, High-Voltage Bay Controller, Manual
813
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...