EXAMPLE 1:
[dw_bsp1uwdl_anpassfaktor, 2, en_US]
Figure 5-2
3-Phase Voltage Transformer: Connection = 3 Phase-to-Ground V VN
If the connection type of the voltage transformer is
3 ph-to-gnd volt. + VN
(parameter:
VT connec-
tion
) and the voltage input V4 is connected to the broken-delta winding of the voltage transformer (da/dn),
the
Matching ratio Vph / VN
is as follows:
When changing the neutral point according to
, this results in the following values:
•
The calculated secondary zero-sequence voltage V
0 sec
is equal to the secondary phase-to-ground voltage.
Expressed as secondary transformer rated voltage, then V
rated sec
/√3.
•
The measured residual voltage on the broken-delta winding is the sum of the voltage drops on the 3
sides. Expressed with the side ratio, the result is V
N, sec
= 3 V
rated,sec
/3.
Calculate the
Matching ratio Vph / VN
parameter as follows:
[fo_bsp1, 2, en_US]
Set
Matching ratio Vph / VN
=
1.73
.
In example 1 V
rated sec
, the phase-to-ground voltage and the secondary voltage on the broken-delta winding
were identical. If these voltages are different, use the actual numerical values in the calculation.
EXAMPLE 2:
Phase-to-ground voltage
V
rated sec
= 100 V
Broken-delta winding (for
example, grounding trans-
former in generator protection)
V
rated sec
= 500 V
The voltage input of the device is designed for a continuous operation,
using 230 V max. Therefore, the voltage on the broken-delta winding (500
V) is reduced to a 5:2 ratio, using an Ohmic divider. In order to calculate the
matching factor, the secondary voltage of 200 V will be applied.
Calculate the
Matching ratio Vph / VN
parameter as follows:
Function-Group Types
5.1 Power-System Data
184
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...