Siemens recommends setting this time to
0 s
so that it has no effect.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:1
Log.-inv.-T #:Mode
•
off
•
on
•
test
off
_:2
Log.-inv.-T #:Operate &
flt.rec. blocked
•
no
•
yes
no
_:119
Log.-inv.-T #:Directional
mode
•
forward
•
reverse
forward
_:8
Log.-inv.-T #:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:118
Log.-inv.-T #:Directional
comparison
•
no
•
yes
no
_:120
Log.-inv.-T #:Release via
input signal
•
no
•
yes
no
_:10
Log.-inv.-T #:Blk. by
meas.-volt. failure
•
no
•
yes
yes
_:26
Log.-inv.-T #:Dynamic
settings
•
no
•
yes
no
_:27
Log.-inv.-T #:Blk. w.
inrush curr. detect.
•
no
•
yes
no
_:3
Log.-inv.-T #:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:6
Log.-inv.-T #:Time dial
0.000 s to 60.000 s
1.250 s
_:113
Log.-inv.-T #:Min. time
of the curve
0.000 s to 60.000 s
1.200 s
_:114
Log.-inv.-T #:Max. time
of the curve
0.000 s to 60.000 s
5.800 s
_:116
Log.-inv.-T #:Threshold
multiplier
1.00 to 4.00
1.10
_:115
Log.-inv.-T #:Additional
time delay
0.000 s to 60.000 s
0.000 s
Dyn.s: AR off/n.rdy
_:28
Log.-inv.-T #:Effect. by
AR off/n.ready
•
no
•
yes
no
_:35
Log.-inv.-T #:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:29
Log.-inv.-T #:Effected by
AR cycle 1
•
no
•
yes
no
_:36
Log.-inv.-T #:Stage
blocked
•
no
•
yes
no
7.7.7.3
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual
733
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...