Table 3-3
Metered Values
IEC 61850
Device Display/
DIGSI
Description
Validity
Good
Invalid
Questionable
X
Value
The metered value is invalid.
X
---
The metered value was not calcu-
lated.
X
≈ Value
The metered value has no refer-
ence.
Indication Columns
The following table shows the meaning of the individual columns in the log:
Indication Column
Meaning
Time stamp
Time stamp of the indication in device time using the local time
zone of the device or the query time for the motor log
Relative time
Relative time to a reference entry
Error number
Number of the error that occurred in the device. This number incre-
ments continuously.
Entry number
Entry identification of buffer entries. This identification displays the
sequence of buffer entries
Indication number
Number of the indication that occurred in the device. This number
increments continuously and is necessary for an analysis by
Siemens.
Indication
Message text
Function Structure
Path of the signal with the signal name
Name
Signal name
Value
Current state of the command. Also pay attention to the value
quality to check whether the value is up to date.
Quality
The quality of the value shows the source of the value and whether
the value is up to date.
Cause
Additional information such as the cause and validity
Number
DIGSI address of the signal
Motor startup time
Time of motor starting
Starting current
Current needed by the motor to start up
Starting voltage
Voltage needed by the motor to start up
Start duration
Time needed by the motor to start up
Logs
General
Indications are saved in logs inside the device and are available for later analyses. Different logs allow catego-
rization of indication logging based on operating states (for example, operational and fault logs) and based on
fields of application.
Table 3-4
Log Overview
Log
Logging
Operational log
Operational indications
Fault log
Fault indications
Ground-fault log
Ground-fault indications
3.1.5
3.1.5.1
System Functions
3.1 Indications
SIPROTEC 5, High-Voltage Bay Controller, Manual
53
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...