Parameter Value
Description
True
The cyclic restoring after the set time of the parameter
(_:111) Energy
restore interval
will also be synchronized with the system time.
Example:
Energy restore interval
= 30 min; current system time:
12:10 o'clock First restore: 12:30 o'clock; next restore: 13:00 o'clock etc.
Note: When the parameter is activated, the following setting values are possible for the parameter
(_:111)
Energy restore interval
: 1 min; 2 min; 3 min; 4 min; 5 min; 6 min; 10 min; 12 min; 15 min; 20 min;
30 min; 60 min.
Input Signals: >Restoring and >Resetting
Binary Inputs
Description
>Restoring
The restoring of the metered values is initiated via a binary input.
>Reset
The metered value memory is set to 0 through the binary input.
You route these logical signals in the DIGSI routing matrix. Open the function group, for example, Line, where
you created the energy value. There, under the tab Measured values you will find the tab Energy, 3-phase.
In this tab, you will find the logical signals in addition to the measured values.
Measured Values, Energy Values, and Supervision of the Primary System
9.9 Energy Values
1044
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...