Application and Setting Notes
Parameter: Threshold
•
Recommended setting value
(_:3) Threshold
=
25 V
The
Threshold
parameter is used to set the voltage which the device uses to recognize the calculated fault
voltage (V
F
) as a failure of the voltage sums. Siemens recommends using the default setting.
Parameter: Delay failure indication
•
Recommended setting value
(_:6) Delay failure indication
=
5.00 s
Set the
Delay failure indication
parameter so that overfunctions due to disturbing influences (such as
switching operations) are avoided. Siemens recommends using the default setting.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Supv. sum V
_:1
Supv. sum V:Mode
•
off
•
on
•
test
off
_:3
Supv. sum V:Threshold
0.300 V to 170.000 V
43.300 V
_:6
Supv. sum V:Delay
failure indication
0.00 sto 100.00 s
5.00 s
Information List
No.
Information
Data Class
(Type)
Type
Supv. sum V
_:82
Supv. sum V:>Block function
SPS
I
_:54
Supv. sum V:Inactive
SPS
O
_:52
Supv. sum V:Behavior
ENS
O
_:53
Supv. sum V:Health
ENS
O
_:71
Supv. sum V:Failure
SPS
O
Voltage Phase-Rotation Supervision
Overview of Functions
The Voltage phase-rotation supervision function monitors the phase sequence of the secondary-circuit
voltages by monitoring the sequence of the zero crossings (with same sign) of the voltages. This enables the
device to detect connections that were inverted during commissioning. The criterion for the check is the
setting of the
Phase sequence
parameter.
Structure of the Function
The Voltage phase-rotation supervision function is located in the Power-system data of each 3-phase
voltage measuring point.
8.3.6.4
8.3.6.5
8.3.6.6
8.3.7
8.3.7.1
8.3.7.2
Supervision Functions
8.3 Supervision of the Secondary System
SIPROTEC 5, High-Voltage Bay Controller, Manual
957
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...