[loocp3pha-210812-01.vsd, 1, en_US]
Figure 7-71
Part-Logic Diagram on the Influence of Inrush-Current Detection Exemplified by the 1st Defi-
nite-Time Overcurrent Protection Stage
Application and Setting Notes
Parameter:
Blk. w. inrush curr. detect.
•
Default setting
(_:661:27) Blk. w. inrush curr. detect.
=
no
Parameter Value
Description
no
The transformer inrush-current detection does not affect the stage.
Select this setting in the following cases:
•
In cases where the device is not used on transformers.
•
In cases where the device is used on transformers and the threshold
value of the stage is set above the maximum inrush current of the
transformer. This, for example, applies to the high-current stage that is
set such according to the short-circuit voltage V
sc
of the transformer
that it only picks up on faults from the high-voltage side. The trans-
former inrush current cannot become larger than the maximum trans-
mittable short-circuit current.
yes
When the transformer inrush current detection detects an inrush current
that would lead to a tripping of the stage, the start of the time delay and
tripping of the stage are blocked.
Select this setting if the device is used on transformers and the threshold
value of the stage is set below the maximum inrush current of the trans-
former. This applies to the overcurrent-protection stage, which is used as a
backup stage with grading time for faults on the undervoltage side of the
transformer.
Influence of Other Functions via Dynamic Settings
Description
The parameters
Threshold
and
Operate delay
used for tripping are so-called
dynamic settings
.
Depending on other functions, the settings of these parameters can be changed dynamically (see
7.4.7.2
7.4.8
7.4.8.1
Protection and Automation Functions
7.4 Overcurrent Protection, Phases
SIPROTEC 5, High-Voltage Bay Controller, Manual
629
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...