[dwmcbstr-040211-01.tif, 1, en_US]
Figure 8-10
Structure/Embedding of the Function
Function Description
The tripping of the voltage-transformer circuit breaker is captured via the binary input signal
>Open
. With an
active input signal the information about the measuring-voltage failure is relayed to the affected functions
(see
). The response to the detection of a measuring-voltage failure is explained
in the specific protection-function descriptions.
Response Time of the Voltage-Transformer Circuit Breaker
The response time of the voltage-transformer circuit breaker can be slower than the pickup time of the
distance protection. This bears the risk of an overfunction. The response time is communicated to the device
with the
Response time
parameter. For a timely detection of the tripping of the voltage-transformer circuit
breaker, the pickup of the distance protection is delayed by that response time.
Application and Setting Notes
The function is always active and need not be switched on.
Input Signal: >Open
•
Input signal:
(_:500) >Open
The input signal
>Open
must be connected to the tripping of the voltage-transformer circuit breaker. As a rule,
this occurs via the routing to a binary input.
Parameter: Response time of the voltage-transformer circuit breaker
•
Recommended setting value
(_:101) Response time
=
0 ms
When the voltage-transformer circuit breaker drops out, the device must block the distance protection imme-
diately to prevent an unwanted tripping of the distance protection due to the absence of the measuring
voltage while the load current is flowing.
The blocking must be faster than the 1st stage of the distance protection. This requires an extremely short
response time of the miniature circuit breaker (≤ 4 ms at 50 Hz, ≤ 3 ms at 60 Hz rated frequency). If the circuit-
breaker auxiliary contact does not fulfill this requirement, you have to set the response time accordingly.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
VT miniatureCB
_:101
VT miniatureCB:Response
time
0.00 s to 0.03 s
0.00 s
Information List
No.
Information
Data Class
(Type)
Type
Definite-T #
_:500
VT miniatureCB:>Open
SPS
I
8.3.4.3
8.3.4.4
8.3.4.5
8.3.4.6
Supervision Functions
8.3 Supervision of the Secondary System
SIPROTEC 5, High-Voltage Bay Controller, Manual
951
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...