User-Defined Function Block [Control]
Overview of Functions
The User-defined function block [control] allows the switching-authority check of a control command and
the check of whether the circuit breaker has reached the position for user-defined controllables.
Function Description
The User-defined function block [control] is located in the folder User-defined functions in the DIGSI 5
Library.
You can instantiate the user-defined function blocks on the top level (in parallel to other function groups) as
well as within function groups and functions.
The task of the function block is to check the switching authority. For control commands, the function block
checks whether the switching direction is the same as the current switch position. You can instantiate every
user-defined signal (for example, SPS, DPC, INC) in the function block and route the corresponding indications
(see following figure).
[scbenutz, 1, en_US]
Figure 6-105
Information Routing with Inserted User-Defined Function Block [Control]: Process Indications
and Some Individual Indications
Application and Setting Notes
The function block contains the parameters
(_:104) Check switching authority
,
(_:105) Check
if pos. is reached
, and
(_:150) Check swi.auth. for Mode
. The parameter settings
Check
switching authority
and
Check if pos. is reached
affect all controllables instantiated in the
function block. Other signal types are not affected by these parameters and objects.
On the other hand, the parameter setting
Check swi.auth. for Mode
affects the controllable
Mode
(controllable)
of the function block.
6.6
6.6.1
6.6.2
6.6.3
Control Functions
6.6 User-Defined Function Block [Control]
432
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...