Addr.
Parameter
C
Setting Options
Default Setting
_:15601:167
90V V.contr.3w:Target
voltage 4 w1
10.000 V to 340.000 V
110.000 V
_:15601:146
90V V.contr.3w:Target
voltage 1 w2
10.000 V to 340.000 V
110.000 V
_:15601:168
90V V.contr.3w:Target
voltage 2 w2
10.000 V to 340.000 V
110.000 V
_:15601:169
90V V.contr.3w:Target
voltage 3 w2
10.000 V to 340.000 V
110.000 V
_:15601:170
90V V.contr.3w:Target
voltage 4 w2
10.000 V to 340.000 V
110.000 V
_:15601:113
90V V.contr.3w:Band-
width
0.2 % to 10.0 %
1.0 %
_:15601:114
90V V.contr.3w:T1 char-
acteristic
•
Linear
•
Inverse
Linear
_:15601:115
90V V.contr.3w:T1 delay
5 s to 600 s
40 s
_:15601:116
90V V.contr.3w:T1
Inverse Min
5 s to 100 s
5 s
_:15601:117
90V V.contr.3w:T2 delay
0 s to 100 s
5 s
_:15601:118
90V V.contr.3w:Fast step
up
•
off
•
on
off
_:15601:119
90V V.contr.3w:Fast step
up limit
-50.0 % to 0.0 %
-6.0 %
_:15601:120
90V V.contr.3w:Fast step
up T delay
0.0 s to 10.0 s
2.0 s
_:15601:121
90V V.contr.3w:Fast step
down
•
off
•
on
on
_:15601:122
90V V.contr.3w:Fast step
down limit
0.0 % to 50.0 %
6.0 %
_:15601:123
90V V.contr.3w:Fast step
down T delay
0.0 s to 10.0 s
0.0 s
_:15601:124
90V V.contr.3w:Function
monitoring
0 min to 120 min
15 min
_:15601:162
90V V.contr.3w:Power-
flow supervision
•
off
•
on
on
_:15601:163
90V V.contr.3w:Regulate
with T2 at start
•
off
•
on
on
_:15601:171
90V V.contr.3w:Set
point mode active
•
off
•
on
on
Line drop comp.
_:15601:125
90V V.contr.3w:Line
drop compensation
•
off
•
LDC-Z
•
LDC-XandR
off
_:15601:126
90V V.contr.3w:Target
voltage rising w1
0.0 % to 20.0 %
4.0 %
_:15601:147
90V V.contr.3w:Target
voltage rising w2
0.0 % to 20.0 %
4.0 %
_:15601:127
90V V.contr.3w:Max
load current
0.0 % to 500.0 %
100.0 %
_:15601:153
90V V.contr.3w:R line
w1
0.0 Ω to 30.0 Ω
0.0 Ω
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual
505
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...