Addr.
Parameter
C
Setting Options
Default Setting
Synchr. conditions
_:5071:122
Synchrocheck 1:Max.
voltage diff. V2>V1
0.000 V to 170.000 V
5.000 V
_:5071:123
Synchrocheck 1:Max.
voltage diff. V2<V1
0.000 V to 170.000 V
5.000 V
_:5071:117
Synchrocheck 1:Max.
frequency diff. f2>f1
0.000 Hz to 2.000 Hz
0.100 Hz
_:5071:118
Synchrocheck 1:Max.
frequency diff. f2<f1
0.000 Hz to 2.000 Hz
0.100 Hz
_:5071:124
Synchrocheck 1:Max.
angle diff. α2>α1
0 ° to 90 °
10 °
_:5071:125
Synchrocheck 1:Max.
angle diff. α2<α1
0 ° to 90 °
10 °
Information List
No.
Information
Data Class
(Type)
Type
Synchrocheck 1
_:5071:81
Synchrocheck 1:>Block stage
SPS
I
_:5071:500
Synchrocheck 1:>Selection
SPS
I
_:5071:502
Synchrocheck 1:>Start / stop syn.proc.
SPS
I
_:5071:503
Synchrocheck 1:>Start syn. process
SPS
I
_:5071:504
Synchrocheck 1:>Stop syn. process
SPS
I
_:5071:506
Synchrocheck 1:>Op. mode 'V1<V2>'
SPS
I
_:5071:505
Synchrocheck 1:>Op. mode 'V1>V2<'
SPS
I
_:5071:507
Synchrocheck 1:>Op. mode 'V1<V2<'
SPS
I
_:5071:508
Synchrocheck 1:>Op. mode 'dir.cls.cmd'
SPS
I
_:5071:501
Synchrocheck 1:>Block close command
SPS
I
_:5071:54
Synchrocheck 1:Inactive
SPS
O
_:5071:52
Synchrocheck 1:Behavior
ENS
O
_:5071:53
Synchrocheck 1:Health
ENS
O
_:5071:328
Synchrocheck 1:In progress
SPS
O
_:5071:324
Synchrocheck 1:Release close cmd.
SPS
O
_:5071:305
Synchrocheck 1:All sync. conditio. OK
SPS
O
_:5071:325
Synchrocheck 1:Voltage difference OK
SPS
O
_:5071:326
Synchrocheck 1:Angle difference OK
SPS
O
_:5071:327
Synchrocheck 1:Frequency diff. OK
SPS
O
_:5071:307
Synchrocheck 1:Cond. V1<V2> fulfilled
SPS
O
_:5071:306
Synchrocheck 1:Cond. V1>V2< fulfilled
SPS
O
_:5071:308
Synchrocheck 1:Cond. V1<V2< fulfilled
SPS
O
_:5071:309
Synchrocheck 1:Frequency f1 > fmax
SPS
O
_:5071:310
Synchrocheck 1:Frequency f1 < fmin
SPS
O
_:5071:311
Synchrocheck 1:Frequency f2 > fmax
SPS
O
_:5071:312
Synchrocheck 1:Frequency f2 < fmin
SPS
O
_:5071:313
Synchrocheck 1:Voltage V1 > Vmax
SPS
O
_:5071:314
Synchrocheck 1:Voltage V1 < Vmin
SPS
O
_:5071:315
Synchrocheck 1:Voltage V2 > Vmax
SPS
O
_:5071:316
Synchrocheck 1:Voltage V2 < Vmin
SPS
O
6.4.7.4
Control Functions
6.4 Synchronization Function
SIPROTEC 5, High-Voltage Bay Controller, Manual
379
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...