Application and Setting Notes
Parameter:
Exponent
•
Default setting
(_:11371:101) Exponent
=
2.0
You use the
Exponent
parameter to specify the exponent for the ΣI
x
method.
A typical value is the default setting of 2. However, due to practical experiences with individual circuit
breakers, slightly different values may be requested.
Parameter:
Threshold
•
Default setting
(_:11371:102) Threshold
=
10 000.00
You use the parameter
Threshold
to define the threshold of the statistic value.
The relation of the tripping current powers to the exponentiated rated normal current I
rated
allows the limiting
value of the ΣI
x
method to correspond to the maximum number of make-break operations. For a circuit
breaker, whose contacts have not yet been worn, the maximum number of make-break operations can be
entered directly as limiting value.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
ΣIx-method
_:11371:1
ΣIx-method:Mode
•
off
•
on
•
test
off
_:11371:101
ΣIx-method:Exponent
1.0 to 3.0
2.0
_:11371:102
ΣIx-method:Threshold
0 to 10000000
10000
Information List
No.
Information
Data Class
(Type)
Type
ΣIx-method
_:11371:54
ΣIx-method:Inactive
SPS
O
_:11371:52
ΣIx-method:Behavior
ENS
O
_:11371:53
ΣIx-method:Health
ENS
O
_:11371:301
ΣIx-method:ΣIx A
BCR
O
_:11371:302
ΣIx-method:ΣIx B
BCR
O
_:11371:303
ΣIx-method:ΣIx C
BCR
O
_:11371:304
ΣIx-method:Warning
ACT
O
9.6.4.2
9.6.4.3
9.6.4.4
Measured Values, Energy Values, and Supervision of the Primary System
9.6 Circuit-Breaker Wear Monitoring
1026
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...