Indications in
DIGSI 5 Information
Device Display Information
Log for parameter changes
Time stamp (date and time),
Relative time,
Entry number,
Function structure,
Name,
Value,
Quality,
Cause,
Number
Time stamp (date and time),
Function structure,
Name,
Value
Spontaneous indication window
(DIGSI 5)
Time stamp (date and time),
Relative time
Indication,
Value,
Quality,
Additional Information
Time stamp (date and time),
Fault number,
Value
Log for safety indications
1
Time stamp (date and time),
Indication number,
Indication
Time stamp (date and time),
Indication
Log for device-diagnostic indica-
tions
2
Time stamp (date and time),
Indication number,
Indication
Time stamp (date and time),
Indication
Log for communication indications
3
Time stamp (date and time),
Indication number,
Indication
Time stamp (date and time),
Indication
Overview of Displayed Quality Attributes
If values are shown on the device display or in DIGSI, the following quality attributes are different for meas-
ured values and metered values.
Table 3-2
Measured Values
IEC 61850
Device Display/
DIGSI
Description
Detail Quality
Validity
Good
Invalid
Questionable
-
X
Value
The measured value is valid.
Failure
X
Fault
The device is defective. Contact
Support.
Inaccurate
X
---
The measured value was not
calculated (for example, the
angle between current and
voltage if one of the 2 variables is
missing).
Bad Reference
X
≈ Value
The measured value can be inac-
curate (for example, outside the
frequency-tracking range).
Out of Range
X
> Value
The measured value exceeds the
measuring range.
1
Only online access
2
Only online access
3
Only online access
System Functions
3.1 Indications
52
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...