Both methods of measurement are characterized by a high measuring accuracy combined with a short pickup
time. Disturbance values such as harmonics, high frequency disturbances, phase-angle jumps during
switching operations and compensation processes due to power swings are effectively suppressed.
Functional Measured Value
The angle-difference method provides the following measured value:
Measured Value
Description
f
Frequency calculated with the angle-difference method
Behavior on Leaving the Operating Range
The sampling-frequency tracking makes a wide frequency operating range possible. If the stage has picked up
before leaving the frequency operating range and the measuring voltage is higher than the set minimum
voltage, the pickup is maintained. A dropout of the pickup is only possible by means of a blocking.
Blocking the Stage
In the event of blocking, a picked-up stage will be reset. The following blocking options are available for the
stage:
•
Externally or internally via the logical binary input
>Block stage
•
Internally when the voltage drops below the
Minimum voltage
Application and Setting Notes
Frequency-Measurement Method
The frequency measurement method is selected with the functional configuration from the DIGSI functions
library. The letter at the end of the function name describes the method of measurement.
Redundant solutions can be implemented by combining 2 different methods of frequency measurement. You
can implement a 2-out-of-2 decision by connecting the operate indications of both functions in a CFC with a
logical AND gate. This increases the reliability of protection.
Frequency-Measurement
Method
Description
Angle difference method
(method A)
Select this method of measurement if the frequency protection stage is
used for the protection of machines.
Filtering method (method B)
Select this method of measurement if the frequency protection stage is
used in an electrical power system.
Parameter: Threshold
•
Recommended setting value
(_:31:3) Threshold
=
51.50 Hz
for f
rated
= 50 Hz
The
Threshold
parameter is used to define the pickup threshold of the overfrequency protection stage in
dependence of the application. 51.50 Hz is a typical warning threshold in 50-Hz systems.
Parameter: Operate delay
•
Recommended setting value
(_:31:6) Operate delay
=
10 s
The
Operate delay
parameter is used to set the stage so that overfunctions due to disturbing influences
(for example, switching operations) are avoided. Fairly high time delays are sufficient for warning indications.
Parameter: Minimum voltage
•
Recommended setting value
(_:2311:101) Minimum voltage
=
37.5 V
For the
Undervoltage blocking
, 65 % of the protected object's rated voltage is recommended.
7.18.4
Protection and Automation Functions
7.18 Overfrequency Protection
826
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...