Interaction of the Quality Attribute Validity and OperatorBlocked
OperatorBlocked check box is not set and receipt of
OperatorBlocked =
TRUE
The OperatorBlocked attribute remains set and is
forwarded.
If the Validity check box is set and the receipt of
validity =
invalid
is set, the respective data object
substitute value is used.
For continued signal processing and influence, it must
be taken into account that in this configuration the
data object substitute value for validity =
invalid
is
set, but the quality attribute OperatorBlocked is not
yet set.
Quality Processing/Affected by the User in CFC Charts
In DIGSI 5, you can control the quality processing of CFC charts. In the project tree, you can find the CFC
building block (see the following figure) under Device name →, Settings → Device settings in the editor:
[sc quali cfc, 1, en_US]
Figure 3-32
Influencing CFC Quality Handling in DIGSI 5
With the
CFC chart quality handling
parameter, you control whether you want to influence the
quality of CFC charts in a
Manual
or
Automatic
(default setting) manner.
If you select
Manual
, the quality attribute of the CFC chart is always valid regardless of the quality of indi-
vidual signals (Validity =
good
)!
Only the Test quality attribute of the CFC chart is processed. If the device is in test mode or the input TEST of
the CHART_STATE CFC building block is set, the quality attribute of the CFC chart is set to
Test
.
If you select
Automatic
, the quality processing of the CFC charts is influenced as follows:
In the case of CFC charts, a distinction has to be made between the general quality processing and certain CFC
building blocks that are specifically designed for quality processing.
General Processing
Most of the CFC building blocks do not have an explicit quality processing. For these building blocks, the
following general mechanisms shall apply.
3.3.3
System Functions
3.3 Processing Quality Attributes
SIPROTEC 5, High-Voltage Bay Controller, Manual
83
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...