Vmax threshold
10.000 kV to 340.000 kV Increments of 0.001 kV
Vmax time delay
0 s to 20 s
Increments of 1 s
Blockings
V< Threshold
10.000 kV to 340.000 kV Increments of 0.001 kV
V< Time delay
0 s to 20 s
Increments of 1 s
I> Threshold
10 % to 500 %
Increments of 1 %
I> Time delay
0 s to 20 s
Increments of 1 s
I< Threshold
3 % to 100 %
Increments of 1 %
I< Time delay
0 s to 20 s
Increments of 1 s
Parallel control
Parallel-transfomer id
0 to 8
Increments of 1
Maximal tap difference
1 to 9
Increments of 1
Reactive I control factor
0.01 to 100.00
Increments of 0.01
VT supervision threshold
0.5% to 10.0%
Increments of 0.1 %
VT supervision time delay
1 s to 600 s
Increments of 1 s
Circul. current threshold
10 % to 500 %
Increments of 1 %
Circul. current time delay
0 s to 1000 s
Increments of 1 s
Measured Values, Two-Winding Transformer
Measured Value Description
Primary
Secondary % Referenced to
V act.
Current, measured positive-
sequence voltage (referenced
to phase-to-phase)
kV
V
Target voltage of the primary
system referenced to the rated
voltage
ΔV act.
Voltage difference between
the target voltage and the
actual voltage
%
%
Voltage difference referenced
to the rated voltage of the
controlled winding
I load
Current measured load current
(positive-sequence system)
A
A
Load current referenced to the
rated value of the function
V max
Maximum positive-sequence
voltage ever measured (refer-
enced to phase-to-phase)
kV
V
Maximum voltage of the
winding referenced to the
rated voltage of the winding
V min
Minimum positive-sequence
voltage ever measured (refer-
ence to phase-to-phase)
kV
V
Minimum voltage of the
winding referenced to the
rated voltage of the winding
V target
Calculated target voltage with
consideration of Z compensa-
tion
kV
V
Target voltage of the winding
referenced to the rated voltage
of the winding
PhAng
Phase angle of the currently
measured load current
°
°
-
I load Σ
Sum of the currently measured
load currents. Active when line
compensation is activated.
A
A
Load current referenced to the
rated current of the function
I circul.
Currently measured circulating
reactive current
A
A
Circulating reactive current
Vact.m
Currently measured control
voltage
kV
V
Current voltage of the control
referenced to the rated voltage
of the function
ΔVactV
Voltage difference
%
%
Voltage difference referenced
to the rated voltage of the
function
Technical Data
11.36 Voltage Controller
1182
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...