Measuring-Voltage Failure Detection
Setting Values
3ph.fail. - VA,VB,VC <
0.300 V to 340 000 V
Increments of 0.001 V
3ph.fail. - phs.curr.release 1 A @ 50 and 100 Irated
0.030 A to 35.000 A
Increments of 0.001 A
5 A @ 50 and 100 Irated
0.15 A to 175.00 A
Increments of 0.01 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
Increments of 0.001 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
Increments of 0.001 A
3ph.fail. - phs.curr. jump
1 A @ 50 and 100 Irated
0.030 A to 35.000 A
Increments of 0.001 A
5 A @ 50 and 100 Irated
0.15 A to 175.00 A
Increments of 0.01 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
Increments of 0.001 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
Increments of 0.001 A
Asym.fail. - time delay
0.00 s to 30.00 s
Increments of 0.01 s
SO 3ph.fail. - time delay
0.00 s to 30.00 s
Increments of 0.01 s
Dropout
The larger dropout differential (=
| pickup value – dropout threshold |
) of the following 2 criteria
is used:
Dropout differential derived from the
Dropout ratio
parameter
If this parameter is not available, a dropout ratio of 95 % applies to the overvoltage protection and a dropout
ratio of 105 % applies to the undervoltage protection.
Minimum absolute dropout differential
150 mV sec.
Times
Pickup time
Approx. 10 ms + OOT
93
at 50 Hz
Approx. 10 ms + OOT at 60 Hz
Dropout time
Approx. 20 ms + OOT
Times
Use in function group Line
Pickup time
Approx. 10 ms + OOT
94
at 50 Hz
Approx. 9 ms + OOT at 60 Hz
Use in other function group types
Pickup time
Approx. 20 ms + OOT
95
at 50 Hz
Approx. 18 ms + OOT at 60 Hz
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1
According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 80 Hz
Slightly expanded tolerances
11.45
93
OOT (Output Operating Time) Additional delay of the output medium used, see chapter
94
95
Technical Data
11.45 Measuring-Voltage Failure Detection
SIPROTEC 5, High-Voltage Bay Controller, Manual
1193
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...