Signal
Type
Description
>Ready
SPS
The active signal indicates that the circuit breaker is ready for an OFF-
ON-OFF cycle.
The signal remains active as long as the circuit breaker is unable to trip.
The signal is used in the Automatic reclosing and Circuit-breaker test
functions.
Another output signal is:
External health
SPS
This can be used to indicate the health of the physical circuit breaker.
For this, you must acquire any failure information for the circuit breaker
via a binary input. This failure information can set the appropriate state
of the
External health
signal with a CFC chart (using the
BUILD_ENS block).
The signal has no effect on the health of the function block.
Circuit-Breaker Tripping Alarm Suppression
Circuit-Breaker Tripping Alarm Suppression
In certain systems, the user may wish to actuate an alarm (for example, a horn) when tripping (circuit-breaker
tripping) occurs. This alarm should not to be issued if the circuit breaker is to be reclosed automatically after
tripping or if it is to be closed or opened via the control. The alarm is only to be issued in the event of final
tripping.
Depending on how the alarm is generated (for example, triggered by a fleeting contact of the circuit breaker),
the
Alarm suppression
signal can be used to suppress the alarm.
The signal is generated if:
•
A definitive protection tripping is not present
•
The automatic reclosing function executes a closure
•
The integrated control executes a closure or opening action
•
External closing is detected via the Manual close function
For further information about its use, please refer to
5.5.9.2 Application and Setting Notes
.
5.5.7.4
Function-Group Types
5.5 Function-Group Type Circuit Breaker, 3-Pole
218
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...