Measured Value Description
Primary
Secondary % Referenced to
ΔVactC
Voltage difference
%
%
Voltage difference referenced
to the rated voltage of the
function
Measured Values for Parallel Control, Proxy
Measured Value Description
Primary
Secondary % Referenced to
V act.
Actual voltage of winding
kV
V
Target voltage of the primary
system referenced to the rated
voltage of the function
1/X trf.
Susceptance, internal value for
GOOSE transmission
1/Ω
I load
Load current
A
-
Load current referenced to the
rated current of the function
PhAng
Phase angle of the load current
relative to the voltage with a
power factor of 1.0
°
°
Phase angle of the load current
100 % = 180°
Measured Values, Three-Winding Transformer
Measured Value Description
Primary
Secondary % Referenced to
Vact.w1
Actual voltage of winding 1
kV
V
Target voltage of the primary
system referenced to the rated
voltage
Vact.w2
Actual voltage of winding 2
kV
V
Target voltage of the primary
system referenced to the rated
voltage
ΔV act.
Voltage difference between
the target voltage and the
actual voltage
%
%
Voltage difference referenced
to the rated voltage of the
controlled winding
I load w1
Load current of winding 1
A
A
Load current referenced to the
rated current of winding 1
I load w2
Load current of winding 2
A
A
Load current referenced to the
rated current of winding 2
Vmax 1
Maximum voltage of winding 1 kV
V
Maximum voltage of winding 1
referenced to the rated voltage
of winding 1
Vmax 2
Maximum voltage of winding 2 kV
V
Maximum voltage of winding 2
referenced to the rated voltage
of winding 2
Vmin 1
Minimum voltage of winding 1 kV
V
Minimum voltage of winding 1
referenced to the rated voltage
of winding 1
Vmin 2
Minimum voltage of winding 2 kV
V
Minimum voltage of winding 2
referenced to the rated voltage
of winding 2
V tar.w1
Target voltage of winding 1
kV
V
Target voltage of winding 1
referenced to the rated voltage
of winding 1
V tar.w2
Target voltage of winding 2
kV
V
Target voltage of winding 2
referenced to the rated voltage
of winding 2
Technical Data
11.36 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual
1183
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...