Addr.
Parameter
C
Setting Options
Default Setting
_:8132:3
Definite-T 2:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
2.000 A
5 A @ 100 Irated 0.150 A to 175.000 A
10.000 A
1 A @ 50 Irated
0.030 A to 35.000 A
2.000 A
5 A @ 50 Irated
0.150 A to 175.000 A
10.000 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
2.000 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
10.000 A
_:8132:4
Definite-T 2:Dropout
ratio
0.90 to 0.99
0.95
_:8132:101
Definite-T 2:Dropout
delay
0.00 s to 60.00 s
0.00 s
_:8132:6
Definite-T 2:Operate
delay
0.00 s to 60.00 s
0.10 s
Dyn.s: AR off/n.rdy
_:8132:28
Definite-T 2:Effect. by AR
off/n.ready
•
no
•
yes
no
_:8132:35
Definite-T 2:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:8132:29
Definite-T 2:Effected by
AR cycle 1
•
no
•
yes
no
_:8132:36
Definite-T 2:Stage
blocked
•
no
•
yes
no
_:8132:14
Definite-T 2:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
2.000 A
5 A @ 100 Irated 0.150 A to 175.000 A
10.000 A
1 A @ 50 Irated
0.030 A to 35.000 A
2.000 A
5 A @ 50 Irated
0.150 A to 175.000 A
10.000 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
2.000 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
10.000 A
_:8132:20
Definite-T 2:Operate
delay
0.00 s to 60.00 s
0.10 s
Dyn.set: AR cycle 2
_:8132:30
Definite-T 2:Effected by
AR cycle 2
•
no
•
yes
no
_:8132:37
Definite-T 2:Stage
blocked
•
no
•
yes
no
_:8132:15
Definite-T 2:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
2.000 A
5 A @ 100 Irated 0.150 A to 175.000 A
10.000 A
1 A @ 50 Irated
0.030 A to 35.000 A
2.000 A
5 A @ 50 Irated
0.150 A to 175.000 A
10.000 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
2.000 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
10.000 A
_:8132:21
Definite-T 2:Operate
delay
0.00 s to 60.00 s
0.10 s
Dyn.set: AR cycle 3
_:8132:31
Definite-T 2:Effected by
AR cycle 3
•
no
•
yes
no
_:8132:38
Definite-T 2:Stage
blocked
•
no
•
yes
no
Protection and Automation Functions
7.6 Directional Overcurrent Protection, Phases
SIPROTEC 5, High-Voltage Bay Controller, Manual
677
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...