Addr.
Parameter
C
Setting Options
Default Setting
_:16351:113
90V V.contr.gc:Band-
width
0.2 % to 10.0 %
1.0 %
_:16351:114
90V V.contr.gc:T1 char-
acteristic
•
Linear
•
Inverse
Linear
_:16351:115
90V V.contr.gc:T1 delay
5 s to 600 s
40 s
_:16351:116
90V V.contr.gc:T1
Inverse Min
5 s to 100 s
5 s
_:16351:117
90V V.contr.gc:T2 delay
0 s to 100 s
5 s
_:16351:118
90V V.contr.gc:Fast step
up
•
off
•
on
off
_:16351:119
90V V.contr.gc:Fast step
up limit
-50.0 % to 0.0 %
-6.0 %
_:16351:120
90V V.contr.gc:Fast step
up T delay
0.0 s to 10.0 s
2.0 s
_:16351:121
90V V.contr.gc:Fast step
down
•
off
•
on
on
_:16351:122
90V V.contr.gc:Fast step
down limit
0.0 % to 50.0 %
6.0 %
_:16351:123
90V V.contr.gc:Fast step
down T delay
0.0 s to 10.0 s
0.0 s
_:16351:124
90V V.contr.gc:Function
monitoring
0 min to 120 min
15 min
_:16351:162
90V V.contr.gc:Power-
flow supervision
•
off
•
on
on
_:16351:163
90V V.contr.gc:Regulate
with T2 at start
•
off
•
on
on
_:16351:171
90V V.contr.gc:Set point
mode active
•
off
•
on
on
Line drop comp.
_:16351:125
90V V.contr.gc:Line drop
compensation
•
off
•
LDC-Z
•
LDC-XandR
off
_:16351:126
90V V.contr.gc:Target
voltage rising w1
0.0 % to 20.0 %
4.0 %
_:16351:147
90V V.contr.gc:Target
voltage rising w2
0.0 % to 20.0 %
4.0 %
_:16351:127
90V V.contr.gc:Max load
current
0.0 % to 500.0 %
100.0 %
_:16351:153
90V V.contr.gc:R line w1
0.0 Ω to 30.0 Ω
0.0 Ω
_:16351:154
90V V.contr.gc:X line w1
-30.0 Ω to 30.0 Ω
0.0 Ω
_:16351:155
90V V.contr.gc:R line w2
0.0 Ω to 30.0 Ω
0.0 Ω
_:16351:156
90V V.contr.gc:X line w2
-30.0 Ω to 30.0 Ω
0.0 Ω
Limiting
_:16351:102
90V V.contr.gc:Lower
tap-position limit
-128 to 127
1
_:16351:103
90V V.contr.gc:Higher
tap-position limit
-128 to 127
15
_:16351:128
90V V.contr.gc:Vmin
limiting
•
off
•
on
on
_:16351:129
90V V.contr.gc:Vmin
threshold w1
10.000 V to 340.000 V
105.000 V
Control Functions
6.9 Voltage Controller
508
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...