Addr.
Parameter
C
Setting Options
Default Setting
Stage 2
_:14552:1
Stage 2:Mode
•
off
•
on
•
test
off
_:14552:2
Stage 2:Operate &
flt.rec. blocked
•
no
•
yes
no
_:14552:9
Stage 2:External trip
initiation
•
no
•
current
•
light
no
_:14552:8
Stage 2:Operating mode
•
light only
•
current and light
current and light
_:14552:11
Stage 2:Sensor
•
point sensor
•
line sensor
•
custom
point sensor
_:14552:7
Stage 2:Threshold light
-34.00 dB to -10.00 dB
-20.00 dB
_:14552:10
Stage 2:Channel
Setting options depend on
configuration
Stage 3
_:14553:1
Stage 3:Mode
•
off
•
on
•
test
off
_:14553:2
Stage 3:Operate &
flt.rec. blocked
•
no
•
yes
no
_:14553:9
Stage 3:External trip
initiation
•
no
•
current
•
light
no
_:14553:8
Stage 3:Operating mode
•
light only
•
current and light
current and light
_:14553:11
Stage 3:Sensor
•
point sensor
•
line sensor
•
custom
point sensor
_:14553:7
Stage 3:Threshold light
-34.00 dB to -10.00 dB
-20.00 dB
_:14553:10
Stage 3:Channel
Setting options depend on
configuration
Information List
No.
Information
Data Class
(Type)
Type
General
_:2311:82
General:>Block function
SPS
I
_:2311:53
General:Health
ENS
O
_:2311:301
General:Current detected
SPS
O
Group indicat.
_:4501:55
Group indicat.:Pickup
ACD
O
_:4501:57
Group indicat.:Operate
ACT
O
Stage 1
_:14551:81
Stage 1:>Block stage
SPS
I
_:14551:501
Stage 1:>External current
SPS
I
_:14551:502
Stage 1:>External light
SPS
I
7.29.7
Protection and Automation Functions
7.29 Arc Protection
918
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...