Figure 3-100
Automatically Recalculated Secondary Values After Changes in the Transformer Data
If you have already set the settings in the secondary view by including the new transformation ratio of the
transformer in the calculation, then answer the question with No. In this case, the protection settings in the
secondary view remain unchanged. DIGSI 5 recalculates the settings (threshold values) of the primary view. In
the example, the primary threshold value is then 300 A (1.5 A * 1000 A/5 A = 300 A).
In the example, the current-transformer ratio changes from 1000 A/1 A to 1000 A/5 A. The following table
summarizes the pickup values that DIGSI 5 will recalculate in the setting view. The new values (in bold)
depend on the answer of your query (see
).
Reply to the Question
Yes
No
Threshold value secondary (active setting view)
7.5 A
1.5 A
Threshold value primary (covered setting view)
1500 A
300 A
Changing the Transformation Ratios of the Transformer on the Device
The device is preset to the secondary value at the time of delivery. Only secondary values can be set directly
on the device.
If you change transformer data directly on the device, it is not followed by a query, like in DIGSI 5 (see
). Instead, the device assumes that all settings remain unchanged in the secondary view.
i
i
NOTE
If the device works with IEC 61850 protocol, you change the transformer data only via DIGSI 5 and not
directly on the device. If you change the transformer data directly on the device, the IEC 61850 configura-
tion of the measurement and metered values can be faulty.
3.9.3
System Functions
3.9 General Notes for Setting the Threshold Value of Protection Functions
SIPROTEC 5, High-Voltage Bay Controller, Manual
161
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...